Wire gauges are typically denoted using the American Wire Gauge (AWG), also known as Brown and Sharpe Wire Guage.
Wire gauges are typically denoted using the American Wire Gauge (AWG), also known as Brown and Sharpe Wire Guage.


The higher the gauge number, the thinner the wire. Telephone/network wires are typically AWG 24 or 26.
Telephone/network wires are typically AWG 24 or 26. Household wiring is thicker and is typically AWG 12 or 14.


== Gauge Table ==
==Gauge Table==
AWG's formula D(AWG)=0.005·92<sup>((36-AWG)/39)</sup> means that:
 
* Every 6 gauge decrease doubles the wire diameter
* Every 3 gauge decrease doubles the wire cross sectional area
 
For 00, 000, 0000 gauge wires, calculate them with negative values -1, -2, -3.
{| class="wikitable"
{| class="wikitable"
!AWG #
!AWG #
!Diameter (inch)
!Diameter (inch)
!Diameter (mm)
!Diameter (mm)
!Resistance Ω/1000m
!Resistance Ω/1km
Copper
Copper
|-
|-
Line 232: Line 238:
|}
|}


== Max current ratings ==
==Max current ratings==
{| class="wikitable"
{| class="wikitable"
! rowspan="3" |AWG
! rowspan="3" |AWG
Line 359: Line 365:
|}
|}


= See Also =
==See Also==


* https://www.engineeringtoolbox.com/wire-gauges-d_419.html
*https://www.engineeringtoolbox.com/wire-gauges-d_419.html

Revision as of 22:23, 12 June 2021

Wire gauges are typically denoted using the American Wire Gauge (AWG), also known as Brown and Sharpe Wire Guage.

Telephone/network wires are typically AWG 24 or 26. Household wiring is thicker and is typically AWG 12 or 14.

Gauge Table

AWG's formula D(AWG)=0.005·92((36-AWG)/39) means that:

  • Every 6 gauge decrease doubles the wire diameter
  • Every 3 gauge decrease doubles the wire cross sectional area

For 00, 000, 0000 gauge wires, calculate them with negative values -1, -2, -3.

AWG # Diameter (inch) Diameter (mm) Resistance Ω/1km

Copper

0000 (4/0) 0.4600 11.6840 0.16
000 (3/0) 0.4096 10.4049 0.20
00 (2/0) 0.3648 9.2658 0.26
0 (1/0) 0.3249 8.2515 0.32
1 0.2893 7.3481 0.41
2 0.2576 6.5437 0.51
3 0.2294 5.8273 0.65
4 0.2043 5.1894 0.81
5 0.1819 4.6213
6 0.1620 4.1154 1.3
7 0.1443 3.6649
8 0.1285 3.2636 2.1
9 0.1144 2.9064
10 0.1019 2.5882 3.3
11 0.0907 2.3048
12 0.0808 2.0525 5.2
13 0.0720 1.8278 6.6
14 0.0641 1.6277 8.2
15 0.0571 1.4495
16 0.0508 1.2908 13
17 0.0453 1.1495
18 0.0403 1.0237 21
19 0.0359 0.9116
20 0.0320 0.8118 34
21 0.0285 0.7229
22 0.0253 0.6438 52
23 0.0226 0.5733
24 0.0201 0.5106 88
25 0.0179 0.4547 108
26 0.0159 0.4049 133
27 0.0142 0.3606 180
28 0.0126 0.3211 216
29 0.0113 0.2859
30 0.0100 0.2546 352
31 0.0089 0.2268
32 0.0080 0.2019 556
33 0.0071 0.1798 663
34 0.0063 0.1601 862
35 0.0056 0.1426 1120
36 0.0050 0.1270 1326
37 0.0045 0.1131 1810
38 0.0040 0.1007 2210
39 0.0035 0.0897 2693
40 0.0031 0.0799 3448

Max current ratings

AWG Typical Max. Current Load Ratings - Copper (amps)
Single Core Multicore
up to 3 cores 4 - 6 cores 7 - 24 cores 25 - 42 cores 43 and above
24 3.5 2 1.6 1.4 1.2 1.0
22 5.0 3 2.4 2.1 1.8 1.5
20 6.0 5 4.0 3.5 3.0 2.5
18 9.5 7 5.6 4.9 4.2 3.5
16 15 10 8.0 7.0 6.0 5.0
14 24 15 12 10 9.0 7.5
12 34 20 16 14 12 10
10 52 30 24 21 18 15
8 75 40 32 28 24 20
6 95 55 44 38 33 27
4 120 70 56 49 42 35
3 154 80 64 56 48 40
2 170 95 76 66 57 57
1 180 110 88 77 66 55